TURBOPEN UNIVERSAL FOAM GENERATOR (UGP)

TU 4854-027-72410778-2013

General

Purpose and scope

The Turbopen universal foam generator (UGP) is a device designed for producing fire extinguishing jets of medium-expansion foam in wide pressure ranges with increased penetrating power and application range as compared to standard technical means such as GPS, GPSS, SVP, etc. It enables to extinguish fires or cover spills of oil and oil products with the maximum coverage of the protected area within the shortest possible time.

The universality of the Turbopen UGP lies in achieving optimal efficiency when using solutions of both synthetic hydrocarbon and film-forming foam concentrates. In terms of resistance to climatic influences, the Turbopen UGP is manufactured in versions U, HL, UHL, T, OM in accordance with GOST 15150-69 (by order).

Distinctive advantages

The main design feature of the Turbopen universal foam generator, which provides its enhanced characteristics, is the patented technology of spraying a jet onto a foam-generating mesh through a nozzle with a dedicated central hole, as well as the use of a conical nozzle to compress the foam jet before it leaves the generator (Russian patent for useful model No. 133743).

Modifications

The Turbopen UGP with a flange connection (or with fire connecting heads of the GM-80 type)

The Turbopen UGP on the PU-A rotary device

The Turbopen UGP on the PU-B rotary device

The Turbopen UGP on the PU-V rotary device

Twin Turbopen UGP (with flow rates 2x20, 2x30 l/s)

The Turbopen UGP on the PU-B with integrated oscillator

The Turbopen UGP on the PU-V with integrated oscillator


The Turbopen UGP are manufactured in the following versions:

  • stationary (at rates of 2, 5, 7, 10, 15, 20, 30, 40 (2x20), 60 (2x30) l/s);
  • manual (at rates of 2, 5, 7, 10 l/s);
  • trolley transported (at rates of 10, 20, 30 l/s).

Specifications

Materials of manufacture

The portable and transportable Turbopen UGP has nozzles and stiffening ribs of aluminum alloy and case of stainless steel.

The stationary Turbopen UGP has nozzles, stiffening ribs, rotary devices of stainless steel.

Key Specifications

Выберите УГП:

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

2

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

8

  • на ПУ-А

10

  • на ПУ-Б

13

  • на ПУ-В

20

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

5

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

10

  • на ПУ-А

12

  • на ПУ-Б

15

  • на ПУ-В

20

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

7

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

13

  • на ПУ-А

15

  • на ПУ-Б

18

  • на ПУ-В

21

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

10

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

13

  • на ПУ-А

15

  • на ПУ-Б

18

  • на ПУ-В

21

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

15

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

18

  • на ПУ-А

21

  • на ПУ-Б

25

  • на ПУ-В

30

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

20

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

20

  • на ПУ-А

25

  • на ПУ-Б

27

  • на ПУ-В

32

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

30

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

23

  • на ПУ-А

28

  • на ПУ-Б

35

  • на ПУ-В

40

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

40

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

38

  • на ПУ-А

-

  • на ПУ-Б

-

  • на ПУ-В

45

Срок эксплуатации, лет, не менее

10

Номинальное давление, МПа

0,6

Рабочее давление, МПа

0,4–1,0

Расход раствора пенообразователя
при номинальном давлении,
л/с, не менее

60

Кратность пены, не менее

30 ± 5

Средняя расчётная высота слоя пены, мм

100

Перемещение пеногенератора

  • на ПУ-А (от центральной оси генератора)

0º–30º

  • на ПУ-Б:

- от центральной оси генератора

0º–30º

- по оси установочного фланца

0º–360º

  • на ПУ-В:

- вокруг оси присоединительного фланца

0º–360º

- вверх, не менее

75º

- вниз, не менее

15º

Масса, кг, не менее

  • на фланцевом соединении

45

  • на ПУ-А

-

  • на ПУ-Б

-

  • на ПУ-В

50

Срок эксплуатации, лет, не менее

10

Name of indicatorValue of indicator
UGP-2UGP-5UGP-7UGP-10UGP-15UGP-20UGP-30UGP-40
(2х20)
UGP-60
(2х30)
Nominal pressure, MPa0,6
Operating pressure, MPA0,4–1,0
Foam concentrate solution flow rate
at nominal pressure,
l/s, min
257101520304060
Foam expansion, min30 ± 5
Average estimated foam layer height, mm100
Angle of rotation of the foam generator
  • installed on PU-А (from the generator central axis))
0º–30º
  • installed on PU-B:
- from the generator central axis0º–30º
- along the axis of the mounting flange0º–360º
  • installed on PU-V:
- around the axis of the mounting flange0º–360º
- upward, min75º
- downward, min15º
Weight, kg, min
  • on flange connection
81013131820233845
  • on PU-А
10121515212528
  • on PU-B
13151818252735
  • on PU-V
202021213032404550
Service life, years, min10

Pressure/range dependency graphs

To compare two graphs, select both values.

Select UGP:
Выберите УГП:
Show all values
График зависимости дальности от давления для УГП-2 «Турбопен»
График зависимости дальности от давления для УГП-5 «Турбопен»
График зависимости дальности от давления для УГП-7 «Турбопен»
График зависимости дальности от давления для УГП-10 «Турбопен»
График зависимости дальности от давления для УГП-15 «Турбопен»
График зависимости дальности от давления для УГП-20 «Турбопен»
График зависимости дальности от давления для УГП-30 «Турбопен»

The ranges UGP-40 (2x20) and UGP-60 (2x30) should be admitted similarly to UGP-20 and UGP-30, respectively.

Flow and pressure graph

Discharge maps

Выберите УГП:

Давление, МПа

0,4

Значение показателя L1/L2

4/6

Давление, МПа

0,5

Значение показателя L1/L2

6/8

Давление, МПа

0,6

Значение показателя L1/L2

8/11

Давление, МПа

0,7

Значение показателя L1/L2

9/14

Давление, МПа

0,8

Значение показателя L1/L2

11/15

Давление, МПа

0,9

Значение показателя L1/L2

12/15

Давление, МПа

1,0

Значение показателя L1/L2

13/16

Давление, МПа

0,4

Значение показателя L1/L2

6/9

Давление, МПа

0,5

Значение показателя L1/L2

10/14

Давление, МПа

0,6

Значение показателя L1/L2

13/18

Давление, МПа

0,7

Значение показателя L1/L2

15/22

Давление, МПа

0,8

Значение показателя L1/L2

16/25

Давление, МПа

0,9

Значение показателя L1/L2

18/27

Давление, МПа

1,0

Значение показателя L1/L2

20/30

Давление, МПа

0,4

Значение показателя L1/L2

9/14

Давление, МПа

0,5

Значение показателя L1/L2

12/17

Давление, МПа

0,6

Значение показателя L1/L2

14/19

Давление, МПа

0,7

Значение показателя L1/L2

16/22

Давление, МПа

0,8

Значение показателя L1/L2

18/30

Давление, МПа

0,9

Значение показателя L1/L2

20/30

Давление, МПа

1,0

Значение показателя L1/L2

23/32

Давление, МПа

0,4

Значение показателя L1/L2

10/15

Давление, МПа

0,5

Значение показателя L1/L2

13/18

Давление, МПа

0,6

Значение показателя L1/L2

15/22

Давление, МПа

0,7

Значение показателя L1/L2

17/25

Давление, МПа

0,8

Значение показателя L1/L2

20/30

Давление, МПа

0,9

Значение показателя L1/L2

23/32

Давление, МПа

1,0

Значение показателя L1/L2

25/33

Давление, МПа

0,4

Значение показателя L1/L2

11/15

Давление, МПа

0,5

Значение показателя L1/L2

15/20

Давление, МПа

0,6

Значение показателя L1/L2

18/23

Давление, МПа

0,7

Значение показателя L1/L2

21/27

Давление, МПа

0,8

Значение показателя L1/L2

24/30

Давление, МПа

0,9

Значение показателя L1/L2

28/35

Давление, МПа

1,0

Значение показателя L1/L2

32/37

Давление, МПа

0,4

Значение показателя L1/L2

15/18

Давление, МПа

0,5

Значение показателя L1/L2

20/25

Давление, МПа

0,6

Значение показателя L1/L2

24/30

Давление, МПа

0,7

Значение показателя L1/L2

27/33

Давление, МПа

0,8

Значение показателя L1/L2

25/35

Давление, МПа

0,9

Значение показателя L1/L2

30/37

Давление, МПа

1,0

Значение показателя L1/L2

35/40

Давление, МПа

0,4

Значение показателя L1/L2

18/23

Давление, МПа

0,5

Значение показателя L1/L2

25/30

Давление, МПа

0,6

Значение показателя L1/L2

28/34

Давление, МПа

0,7

Значение показателя L1/L2

32/40

Давление, МПа

0,8

Значение показателя L1/L2

35/45

Давление, МПа

0,9

Значение показателя L1/L2

38/48

Давление, МПа

1,0

Значение показателя L1/L2

42/50

Давление, МПа

0,4

Значение показателя L1/L2

15/18

Давление, МПа

0,5

Значение показателя L1/L2

20/25

Давление, МПа

0,6

Значение показателя L1/L2

24/30

Давление, МПа

0,7

Значение показателя L1/L2

27/33

Давление, МПа

0,8

Значение показателя L1/L2

25/35

Давление, МПа

0,9

Значение показателя L1/L2

30/37

Давление, МПа

1,0

Значение показателя L1/L2

35/40

Давление, МПа

0,4

Значение показателя L1/L2

18/23

Давление, МПа

0,5

Значение показателя L1/L2

25/30

Давление, МПа

0,6

Значение показателя L1/L2

28/34

Давление, МПа

0,7

Значение показателя L1/L2

32/40

Давление, МПа

0,8

Значение показателя L1/L2

35/45

Давление, МПа

0,9

Значение показателя L1/L2

38/48

Давление, МПа

1,0

Значение показателя L1/L2

42/50

Select pressure

Show all values
Indicator value L1/L2
UGP-2UGP-5UGP-7UGP-10UGP-15UGP-20UGP-30UGP-40
(2х20)
UGP-60
(2х30)
4/66/99/1410/1511/1515/1818/2315/1818/23
6/810/1412/1713/1815/2020/2525/3020/2525/30
8/1113/1814/1915/2218/2324/3028/3424/3028/34
9/1415/2216/2217/2521/2727/3332/4027/3332/40
11/1516/2518/3020/3024/3025/3535/4525/3535/45
12/1518/2720/3023/3228/3530/3738/4830/3738/48
13/1620/3023/3225/3332/3735/4042/5035/4042/50

Notes

  • h = 2,5–3 m;
  • L1 – effective range;
  • L2 – range according to discharge map (including spreading);
  • W is taken to scale relative to values L1 and L2;
  • the values are given when the UGP is installed at an angle of 30º upward relative to the horizon.

Layout and technical conditions for the application of the Turbopen UGP with an oscillator

Oscillator Specifications:

  • the use of the oscillator is possible at a flow rate of 10 l/s and more (if you need to install an oscillator at a flow rate of 5 l/s, please contact our specialists);
  • when using an oscillator, it is necessary to take into account the pressure drop of 0.1 MPa, i.e. the pressure upstream of the Turbopen UGP must be taken at 0.1 MPa more;
  • in the labeling of the Turbopen UGP it is necessary to indicate the value of the oscillation positions (1, 2, 3 or 4);
  • when developing discharge maps using an oscillator, the extreme edges of zones 1, 2, 3, 4 should be taken as the axis of the discharge maps shown in paragraph Discharge maps

Для просмотра полного описания технических характеристик отправьте заявку или войдите под своим профилем

Design Information

To protect generator nozzles from ingress, it is necessary to install a Tauer universal fire filter (PFU) TU 4854-012-72410778-07 with a cell size of 2x2 mm on upstream solution piping of the firefighting installations.

Video

Версия для
печати
  • General
  • Modifications
  • Specifications
  • Design Information
  • Video


IF YOU HAVE QUESTIONS Or PROPOSALS, PLEASE FILL IN OUR FORM

Filling out the form means you agree with the confidencial policy of the web-site www.pnx-spb.ru and agree to receive the email by Pozhneftehim-Expert to the indicated email. You can unsubscribe from the email at any time. You can also get access to emails that were send before. The contact email for the Pozhneftehim-Expert project is expert@pozhneftekhim.ru.